    What is the normal temperature differential between the inlet and outlet vent on a CruiseAir unit? My coach is in the shade in a garage and I am only seeing a 10 deg temp difference. Some where in the back of the old brain I think I remember a CruiseAir system is working at its optimum level when the temp differential is 20 -22 Deg.

    Chuck


    2000 Featherlite H3-45

    2024 Jeep Grand Cherokee

    Leesburg, FL
    Archived replied 4 years, 5 months ago 4 Members · 3 Replies
  • 3 Replies
  • Dick

    Member
    April 1, 2022 at 1:47 pm

    I think you’re right. I’ve never checked the Delta-T (but should). We have a heat pump in our house and I am seeing about 24/25*F Delta-T. I wonder what Fred at AAP would say is a good Delta-T.

  • Art

    Member
    April 2, 2022 at 8:13 am

    20 degrees is the normal number quoted. I have never found anything about a Cruisair to be normal.

  • Archived

    Member
    April 6, 2022 at 6:10 pm

    I asked Fred Pickering from AAP the Cruise-Air expert that question. This was his answer: “On a warm summer day, let’s say 80-90 degrees and high humidity, we would expect to see anywhere between 14-18 degrees differential, which would indicate the system was charged correctly and operating to the best it could.”