Prevost OTR issues
I live in the Austin, TX area. I am having Prevost OTR issues. And need to find a shop that can add 134a to this system as it appears low. Does anyone have a suggestion, or do I need to go to Dallas/Houston?
The rundown: It all started because I felt the dash ac is not putting out enough cooling. So I opened the cargo door and looked at the dryer and the wet label is showing blue, but it appears I am low on 134a as I see lots of bubbles in the mix. If I look at the recovery tank below the dryer (while AC is running), both the red balls (one at the top and bottom of tank) are resting on the floor of the sight glass and I see no liquid in the sight glasses. The fans are cycling on the condenser like every 30 seconds or so, but the inside temp is still quite a bit above the setting on the dash control. At one point the fans where turning on and off almost like a short, in rapid succession and intermittently. I did not think to go look at the Ac comm. panel on the driver side behind the rear wheels during all this (still new to Prevost, just bought it in late spring), I will do that next time I am out at the shop.
The following readings where taken with an outside temp 80f, bus shaded (been in the shop and moved outside for this test), engine temp ~190f and @ fast idle during test, using a Fluke multimeter with thermal probe to take measurements:
Coach Ac:
Inlet measured at the front stairwell intake: 66f
Outlet measured at the vent right behind the driver side kitchen sink which is as close as I can get to the evap. coil (without opening the bay door and inserting the probe in the evap. bay): 46f (20f delta, this seems ok, but with this huge unit would seem it should be a little more)
Dash Ac (the problem child that started me looking into this):
Inlet measured at the base of the right dash near the stepwell: 66f
Outlet measured at the driver, passenger and defroster: 58f (8f delta, this no bueno)
Also on a similar note, the defroster output can never be shut off. When I pulled the CD Changer/GPS in the stepwell area coming into the bus to look into this, it appears there is no dampner door mechinism to shutoff the defroster, and that it will always be on. I’m I right, or is there one somewhere that I need to track down and repair?
Edited 9/25/13-15:30 hrs:
Forgot to state that I had both units in re-circulate. I verified the coach was not recirculating by checking the side inlet between the 3rd and 4th bay on the drivers side was not taking in air, which it was not. I am not sure where to check the air recirc for the dash air yet.