I’ve not has any issues with regard to AC amperage, no matter how much I loaded up both legs. The problem, is the analog gauges are unreliable and never get above 15 amps AC. I put my Fluke on the hot side of each leg at the electrical panel and the actual amps were almost twice what the meters would show. So I started taking things apart and decided to replace both the volts and amps meters, at least for a nice cleaner look. One of the old volt meters was in poor shape on the backside of the barrel anyways.
After searching for a few days I found meters that would fit, the barrel dimensions had to be just right to fit the existing holes and the installation was a breeze. Unfortunately, the new meters didn’t fix my low amp reading, not a big surprise and I learned why at a very good electronic shop near home. My transformers are in the AC electrical panel in the bedroom and the meters of course are above the dash. The transformers are good and reading the correct amps. The problem is the wire run to the front of the bus. The shop did some calculations for me and the drop in amps is caused by approximately 30′ of wire that reduces the meter needle deflection to about 1/2 of the actual amps being used. Great design Royale, I can’t believe no one in the past noticed the 20 amp readings when just about everything in the bus was running and both AC legs were just about to the 50 amp max each.
So, if you have lazy amp needles, you may have the same issue. My plan is to add digital meters for the amps and locate in the galley where it’s easy to monitor.