Generator Not Synching With Inverters
I am starting to experience a problem with the inverters when I start the generator. It does not happen every time but maybe every third or fourth time now. My coach is a 2003 Marathon with the Kohler 20kw genset and and the original two 4000 watt Trace inverters. The generator which has 6900 hours gets a lot of use compared to many on this site but I depend on it and maintain it frequently. Specifically, if I am watching the Tecklink system when I start the generator I can see it spool up. Normally after both legs reach 120 volts, the inverters will begin drawing current and you can see the amp draw on each beginning to rise after about 30 seconds. Recently after starting the generator, and a minute or so afterward, I could tell from the sound of it running that there was little to no load on it. Sure enough, the Techlink display verified there was no draw from the inverters. I walked back to the inverter panel and both “AC2 in” indicators were still flashing. After another minute, and no change, I put the first inverter in “Search” mode and the “AC2 in” LED almost immediately went solid. I returned the inverter status to “On” and did the same with the second inverter. Everything functioned normally after this.
Several weeks later, and after other successful generator usages, the same scenario played out. Has anyone ever experienced this problem? Since both inverters are initially rejecting the generator power, my first guess is a problem with the transfer switch. Let me hear your all’s thoughts. Thanks.